Printer's Parts Store, Inc.

 

7409 NW 103 Terrace      Oklahoma City, OK  73162

 

405-721-1701     1-800-375-3787          ppsokc@aol.com  

 

SAFETY TRANSFERE

 

 

SAFETY TRANSFERE
Home Up DOWNLOADS NEW EQUIPMENT USED EQUIPMENT

 

 

VBII safety switch

        general duty - 240 volt

        heavy duty - 240 volt

        heavy duty - 600 volt

Double throw transfer switches

 

 

VBII safety switch

 

 

Available In:

So Reliable, It Will Be Around For Generations To Come

We've Built The VBII Safety Switch To Be So Durable, So Reliable - It Just Might Be Around For The Next Millennium. In Fact, The VBII Gives You The Confidence That Once It Is Installed - You're Done! Here's Why:

  • Rugged Metal Handle With Large Red Grip Which Provides Highly Visible ON/OFF Indication.

  • Generous Wire Gutters That Meet and/or Exceed NEC Wire Bending Space Requirements.

  • A Unique Enclosure Design That Adds Rigidity and Strength. It Also Offers A Touch-Safe Edge For The Installer's Hand.

  • Visible Blade, Double-Break Switching Action.

  • Spring Reinforced Fuse Clips That Assure Reliable Contact For Cool Operation.

  • Front Removable Mechanical Lugs That Are Field Convertible To Copper Mechanical Lugs Or Compression (Crimp) Connectors

  • A Hinged Clear Line Shield With Probe Holes For Inspecting Or Testing Line Side Terminals.

 

Really Tough

Built To Last. Everything About The VBII Safety Switch Has

Been Designed For The Engineer and Installer. We Have Rolled The

Enclosure's Metal Edges and Corners To Minimize Cuts, Nicks and

Scrapes To The Installer's Hands and Conductors. We Have Added

Generous Wiring Gutters To Meet Or Exceed UL and NEC Wire

Bending Space Requirements. The Enclosure Is More Rigid and Resilient

and All Parts Are Replaceable For Easier Service. Our Quick-Make

Quick-Break Switching Action Coupled With Our Double-Break

Visible Blade Design Ensures Reliable Operation In Both General Duty

and Heavy Duty Applications. Tough In The Field Yet Easy On You.

 

                                                                          

 

 

VBII safety switch general duty - 240 volt

 

Features:

  • Highly Visible Easy-To-Grip Handle

  • Visible Blade Construction

  • Door Opens Greater Than 180

  • Quick-Make, Quick-Break Mechanism

  • 200% Optional Neutrals (200-600 Amps)

  • Positive Two and Three Point Mounting

  • Padlock Style Cover Latch and Handle

  • Generous Wiring Gutter

  • Lugs Suitable For Copper Or Aluminum At 60C Or 75C

  • Replacement Parts

  • UL Listed

 

Amp

Rating

NEMA 1

Indoor

NEMA 3R

Outdoor

Horsepower Rating

240V AC

Model

Number

 

Model

Number

 

1-Phase, 2-Wire

3-Phase, 3-Wire

Std.

Max.

Std.

Max.

240 Volt Fusible - 2-Pole, 2-Fuse, Solid Neutral

30

GF221N

 

GF221NR

 

1.5

3

3

7.5

60

GF222N

 

GF222NR

 

3

10

7.5

15

100

GF223N

 

GF223NR

 

7.5

15

15

30

200

GF224N

 

GF224NR

 

15

--

25

60

400

GF225N

 

GF225NR

 

15

--

50

125

600

GF226N

 

GF226NR

 

15

--

75

200

240 Volt Fusible - 3-Pole, 3-Fuse, Solid Neutral

30

GF321N

 

GF321NR

 

1.5

3

3

7.5

60

GF322N

 

GF322NR

 

3

10

7.5

15

100

GF323N

 

GF323NR

 

7.5

15

15

30

200

GF324N

 

GF324NR

 

15

--

25

60

400

GF325N

 

GF325NR

 

15

--

50

125

600

GF326N

 

GF326NR

 

15

---

75

200

240 Volt Non-fusible - 3-Pole, 3-Wire, No Neutral - Also Used For 2-Pole Applications

30

GNF321N

 

GNF321R

 

--

3

7.5

--

60

GNF322N

 

GNF322R

 

--

10

15

--

100

GNF323N

 

GNF323R

 

--

15

30

--

200

GNF324N

 

GNF324R

 

--

15

60

--

400

GNF325N

 

HNF365R

 

--

15

125

--

600

GNF326N

 

HNF366R

 

--

15

200

--

 

 

 

 

 

VBII safety switch heavy duty - 240 volt

 

Features:

  • Highly Visible Easy-To-Grip Handle

  • Visible Blade Construction

  • Door Opens Greater Than 180

  • Quick-Make, Quick-Break Mechanism

  • 200% Optional Neutrals (200-600 Amps)

  • All Copper Current Carrying Parts OnHeavy Duty Switches (Except Wire Grips)

  • Positive Two and Three Point Mounting

  • Padlock Style Cover Latch and Handle

  • Generous Wiring Gutter

  • Lugs Suitable For Copper Or Aluminum At 60C Or 75C

  • Replacement Parts

  • UL Listed

Amp

Rating

NEMA 1

Indoor

NEMA 3R

Outdoor

Horsepower Rating

240V AC

Model

Number

 

Model

Number

 

 

 

1-Phase, 2-Wire

3-Phase, 3-Wire

Std.

Max.

Std.

Max.

240 Volt Fusible - 2-Pole, 2-Fuse, Solid Neutral

30

HF221N

 

HF221NR

 

1.5

3

3

7.5

60

HF222N

 

HF222NR

 

3

10

7.5

15

100

HF223N

 

HF223NR

 

7.5

15

15

30

200

HF224N

 

HF224NR

 

15

--

25

60

400

HF225N

 

HF225NR

 

15

--

50

125

600

HF226N

 

HF226NR

 

15

--

75

200

800 HF227N   HF227NR   -- -- 100 250
1200 HF228N   HF228NR   -- -- 100 250

240 Volt Fusible - 3-Pole, 3-Fuse, Solid Neutral

30

HF321N

 

HF321NR

 

1.5

3

3

7.5

60

HF322N

 

HF322NR

 

3

10

7.5

15

100

HF323N

 

HF323NR

 

7.5

15

15

30

200

HF324N

 

HF324NR

 

15

--

25

60

400

HF325N

 

HF325NR

 

15

--

50

125

600

HF326N

 

HF326NR

 

15

---

75

200

800 HF327N   HF327NR   -- -- 100 250
1200 HF328N   HF328NR   -- -- 100 250

 

 

 

 

 

VBII safety switch heavy duty - 600 volt

 

Features:

  • Highly Visible Easy-To-Grip Handle

  • Visible Blade Construction

  • Door Opens Greater Than 180

  • Quick-Make, Quick-Break Mechanism

  • 200% Optional Neutrals (200-600 Amps)

  • All Copper Current Carrying Parts On Heavy Duty Switches (Except Wire Grips)

  • Positive Two and Three Point Mounting

  • Padlock Style Cover Latch and Handle

  • Generous Wiring Gutter

  • Lugs Suitable For Copper Or Aluminum At 60C Or 75C

  • Replacement Parts

  • UL Listed

Amp

Rating

NEMA 1

Indoor

NEMA 3R

Outdoor

NEMA 12

Industrial

Horsepower Rating

3-Phase

Model

Number

 

Model

Number

 

Model

Number

 

480V AC

600V AC

Std.

Max.

Std.

Max.

600 Volt Fusible - 3-Pole, 3-Fuse, No Neutral - Also Used For 2-Pole Applications

30 HF361   HF361R   HF361J   5 15 7.5 20
60 HF362   HF362R   HF362J   15 30 15 50
100 HF363   HF363R   HF363J   25 60 30 75
200 HF364   HF364R   HF364J   50 125 60 150
400 HF365   HF365R   HF365J   100 250 125 350
600 HF366   HF366R   HF366J   150 400 200 500
800 HF367   HF367R   HF367J   200 500 250 500
1200 HF368   HF368R   --   -- -- -- --

600 Volt Non-Fusible - 3-Pole, 3-Wire

30 HNF361   HNF361R   HNF361J   -- 20 -- 30
60 HNF362   HNF362R   HNF362J   -- 50 -- 60
100 HNF363   HNF363R   HNF363J   -- 75 -- 100
200 HNF364   HNF364R   HNF364J   -- 125 -- 150
400 HNF365   HNF365R   HNF365J   -- 250 -- 350
600 HNF366   HNF366R   HNF366J   -- 400 -- 500
800 HNF367   HNF367R   HNF367J   -- 500 -- 500
1200 HNF368   HNF368R   --   -- 500 -- 500

 

 

 

 

Double throw transfer switches

 

 

 

Wire Ranges (Line, Load And Neutral)

Per NEC Requirements:

Switch

Ampere

Rating

Wire Range (Cu / A1)

New VBII Design

Line, Load And Neutral

30 - 200 A - 2, 3 & 4 Pole Switches

30

(1) #14-6

60

(1) #14-2

100

(1) #14-1/0 AWG

100

(1) #14-1/0 AWG

200

(1) #6-250 kcmil

400 - 1200 A - 2 & 3 Pole Switches

400

(1) 1/0 AWG - 750 kcmil or

(2) 1/0 AWG - 250 kcmil

600

(2) 1/0 AWG - 500 kcmil

800

(2) 1/0 AWG - 750 kcmil or

(3) 1/0 AWG - 500 kcmil

1200

(3) 1/0 AWG - 600 kcmil or

(4) 1/0 AWG - 500 kcmil

400 - 800 A - 4 Pole Switches

400

(1) 1/0 AWG - 300 kcmil or

(2) 1/0 AWG - 750 kcmil

600

(2) 250 - 500 kcmil

800

(3) 250 - 500 kcmil

 

Description:

Double Throw Switches Are Intended To Transfer Loads From One

Power Source To Another. All 2 and 3 Pole Double Throw Switches

Are Suitable For Use As Service Equipment. All Are UL Listed.

Switches Are Rated For Use On Systems Up To 10,000 A When

Protected With Class H Fuses Or 100,000 A When Protected With

Class R Or Class T Fuses (2). They Can Also Be Used To Connect

A Single Source Of Power To Either Of Two Loads. In This

Application It Is Necessary To Field Modify Fusible Switches

So That The Fuses Are On The Load Side Of The Switching

Mechanism. A Cover Interlock Is Provided On All Ampere Ratings.

The Operating Handle May Be Padlocked In The Off Position.

 

 

Fuse Capabilities Of Fusible Switches:

Amp

Rating

Fuse Type

H

R

T

J

30 & 60 A, 240 V

Std.

Yes (Kit)

No

No

30 & 60 A, 6000 V

Std.

Yes (Kit)

No

Yes (3)

100 & 200 A

Std.

Yes (Kit)

Yes (Kit)

Yes (3)

 

Maximum Horsepower Ratings:

Ampere

Rating

1 Phase AC

240V

3 Phase AC

250V

DC

240V

480V

600V

Fused

30

3

7.5

15

20

5

60

10

15

30

50

10

100

15

30

60

75

20

200

15

60

125

150

40

400

--

125

125

125

50

600

--

125

--

--

50

Non_Fused

30

5

10

20

30

5

60

10

20

50

60

10

100

15

40

75

100

20

200

15

60

125

150

40

400-800

--

125

250

350

50

Voltage

Number

Of Poles

Amps

NEMA 3R - Outdoor

Less Neutral

NEMA 3R - Outdoor

With Neutral

Model

Number

Model

Number

General Duty Non-Fusible

240 Volt AC

2

100

DTGNF223R

DTGNF223NR

200

DTGNF224R

DTGNF224NR

3

100

DTGNF323R

DTGNF323NR

200

DTGNF324R

DTGNF324NR

 

Voltage

Number

Of Poles

Amps

NEMA 1

Indoor

NEMA 3R

Outdoor

NEMA 12 / 3R

Industrial

NEMA 4X

Stainless Steel

Model

Number

 

Model

Number

 

Model

Number

List

Price

Model

Number

 

Heavy Duty Fusible (30-200 A) With Class H Fuse Spacings (2)

 

 

 

240 Volt AC

Or

250Volt DC

 

 

 

 

 

2

200

DTF224

 

DTF224R

 

--

--

--

 

3

30

DTF321

 

DTF321R

 

--

--

--

 

60

DTF322

 

DTF322R

 

--

--

--

 

100

DTF323

 

DTF323R

 

--

--

--

 

200

DTF324

 

DTF324R

 

--

--

--

 

400

DTF325

 

FR325DTK (4)

 

--

--

--

 

600

DTF326

 

FR326DTK (4)

 

--

--

--

 

600 Volt AC

Or

250Volt DC

 

 

 

 

3

30

DTF361

 

--

 

--

--

--

 

60

DTF362

 

--

 

--

--

--

 

100

DTF363

 

DTF363R

 

--

--

F353SSDTK

 

200

DTF364

 

DTF364R

 

--

--

F354SSDTK

 

400

DTF365

 

FR355DTK (4)

 

--

--

F355SSDTK (4)

 

Heavy Duty Non-Fusible (2)

240 Volt AC

Or

250Volt DC

 

 

 

 

 

 

 

 

 

 

 

2

30

DTNF221

 

--

 

--

 

--

 

60

DTNF222

 

--

 

--

 

--

 

100

DTNF223

 

--

 

--

 

--

 

200

DTNF224

 

DTNF224R

 

--

 

--

 

400

DTNF225

 

DTNF225R

 

--

 

--

 

3

30

DTNF321

 

--

 

--

 

--

 

60

DTNF322

 

--

 

--

 

--

 

100

DTNF323

  DTNF323R  

--

 

--

 

200

DTNF324

 

DTNF324R

 

--

 

--

 
400 DTNF325  

--

 

--

 

--

 
600 DTNF326  

--

 

--

 

--

 
800 DTNF327  

--

 

--

 

--

 

600 Volt AC

Or

250Volt DC

 

3 30 DTNF361   DTNF361R   DTNF361J   DTNF361S  
60 DTNF362   DTNF362R   DTNF362J   DTNF362S  
100 DTNF363   DTNF363R   DTNF363J   DTNF363S  
200 DTNF364   DTNF364R   DTNF364J   DTNF364S  
400 DTNF365   DTNF365R   NF355HDTK   NF355SSDTK  
600 DTNF366   DTNF366R  

--

--

--

 
800 DTNF367   DTNF367R  

--

--

--

 
1200 DTNF368   DTNF368R  

--

--

--

 
4 (5) 30

--

  NFR451DTK  

--

--

--

 
60

--

  NFR452DTK  

--

--

--

 
100

--

  NFR453DTK  

--

--

--

 
200 NF454DTK    NFR454DTK  

--

-- NF454SSDTK  
400 NF455DTK   NFR455DTK  

--

--

--

 
600 NF456DTK   NFR456DTK  

--

--

--

 
800 NF457DTK   NFR457DTK  

--

--

--

 

 

▲Built To Order - Please Allow 3-4 Weeks For Delivery

(1) Use HS Type Hubs For 30-200A Switches - 400 A and Larger Switches Do Not Have Hub Provisions.

(2) All Heavy Duty Double Throw Switches With A Catalog Number Starting With "DT" Are Rated 200,000 AIC Max.

     When Protected By Class R, J Or T Fuses. Fuse Ampere Rating Must Not Exceed Switch Ampere Rating.

(3) Move Load Base.

(4) Model Number F355SSDTK Will Accept Class T Fuses Only.

(5) 4 Pole Switches Are Not Approved For Service Entrance.

 

 

Description Model

Number

 
Accessories - 2 & 3 Pole Switches Only (1)

neutral kits

30 A hnc612  
60 & 100 A hn263  
200 A hnc264  
400 & 600 A hn678  
800 & 1200 A hnd678  

equipment

ground kit

30 - 200 A     (2) #14-4 AWG HG61234  
400 & 600 A     (4) #14-2/0 HG656  
800 - 1200 A      (8) #6-350 Kcmil HG678  

auxiliary contacts (HD only)

(2 required per switch) (4)

30 - 200 A     With (1) NO & (1) NC Contacts HA161234  
30 - 200 A    With (2) NO & (2) NC Contacts HA261234  
400 - 1200 A    With (1) NO & (1) NC Contacts HA165678  
400 - 1200A    With (2) NO & (2) NC Contacts HA265678  

class r fuse clip kits

(2 required per switch)

30A, 240 V Kit HR21  
30A, 6000 V Kit / 60A, 240 V Kit HR612  
60 A, 600 V Kit HR62  
100 A Kit HR63  
200 A Kit HR64  

class t fuse adapter kits

(2 required per pole)

 

100 A, 240 V Kit HT23  
100 A, 600 V Kit HT63  
200 A, 240 V Kit HT24  
200 A,  600 V Kit HT64  

type 3r hubs (30 - 200 A)

For 3/4" Conduit HS075  
For 1" Conduit ECHS100  
For 1 1/4" Conduit ECHS125  
For 1 1/2" Conduit ECHS150  
For 2" Conduit ECHS200  
For 2 1/2" Conduit ECHS250  

accessories - 4 pole switches only (2)

auxiliary switch

(2 required per switch)

30 - 800 A     (1) NO, (1) NC (4) DS200EK1  
30 - 800 A     (2) NO, (2) NC (4) DS200EK2  

ground lug kit (3)

30-60-100 A DS100GK  
200 A DS200GK  
400 - 600 - 800 A DS468GK  

hubs

30 - 60 - 100 A     Use Type HR Hubs    
200 - 400 A     Use Type SSH 4, 4X Hubs    
600 - 800 A     Use Type SSH 4, 4X Hubs    

neutrals

(for fusible stainless and

400 a type 12 & 4X only)

30 - 60 - 100 A DT100NK  
200 A DT200NK  
400 A Fusible DT800NK  

replacement parts - 2 & 3 pole switches only (1)

type 1, 3r & 12 replacement handle

300 - 200 A HHD61234  

 

(1) Not For Fusible Stainless Or 400 A NEMA 12 Or 4X Switches.

(2) Also For Fusible Stainless & 400 A NEMA 12 Or 4X Switches.

(3) The Following Ground Lugs Are Provided As Standard In:

200 A and Larger Switches 200 - (1) #14-4 Cu/Al

400-800 A - (3) #6-250MCM Cu/Al

(4) One Auxiliary Required For Normal and One Required For Emergency Switch Line Base.